HVAC Diagnostics: The Five Fundamentals

Suction pressure / low side

  • The suction pressure indicates the evaporating temperature of the refrigerant in the evaporator.
  • Low pressure can cause freezing of the coil.
  • Rule of thumb: 35°F below return (DTD) with 400 CFM/ton ±5°F.
  • For 350 CFM/ton, DTD between 38°F and 40°F ±5°F.
  • Oversized evaporators can slightly reduce the DTD.

Discharge pressure / High side

  • Helps determine the compression ratio and conditions in the condenser.
  • Rule of thumb: 15-20°F above outside ambient ±3°F.
  • CTOA according to SEER:
    • 6-10 SEER (pre 1991): 30°F
    • 10-12 SEER (1992-2005): 25°F
    • 13-15 SEER (2006-present): 20°F
    • 16+ SEER (2006-present): 15°F

Superheat

  • Indicates if liquid is entering the compressor and if the evaporator is well fed.
  • 0°F superheat = risk of slugging damage.
  • With TXV: maintain between 5°F and 15°F (ideally 10°F ±5°F).
  • With fixed hole: use manufacturer's table.

Subcooling (Subcooling)

  • Indicates if the liquid line contains only liquid refrigerant.
  • 0°F = mixture of liquid and vapor.
  • High subcool = refrigerant flowing slowly in condenser.
  • Typical values with TXV: 8-14°F (rule of thumb: 10°F ±3°F).
  • With fixed orifice can range from 5-23°F.

Delta T / Temperature differential

  • Evaluates performance and air flow.
  • Typical Delta T: 16-22°F.
  • - Delta T high = low air flow.
  • Low Delta T = poor performance.
  • In humid climates or low CFM, higher Delta T is expected.

Diagnosis with the Five Fundamentals

  • Correlate all parameters to find the probable cause.
  • In TXV systems, superheat and suction pressure tend to be stable.
  • Problems with TXV or subcool = 0°F can break that equilibrium.

Diagnostic Table by Parameter

ParameterPossible causes
Low suction pressureLack of refrigerant, low heat load, evaporator clogging or TXV
High suction pressureRefrigerant overcharge, hot air return, TXV failing open
Low discharge pressureLack of refrigerant, cold environment, excessively open expansion valve
High discharge pressureOvercharge, low condenser flow, refrigerant mixture or non-condensables
Low reheatOverload, TXV too open, restricted air flow
High reheatLack of coolant, TXV restricted, return too hot
Low subcoolingLack of refrigerant, TXV open too much, compressor with poor compression
High subcoolingOverload, liquid line restriction, TXV closed or restricted
Delta T highInsufficient air flow, low humidity
Delta T lowLow load, excess flow, activated electrical resistance, high humidity